Safety Alert - Technical No. 20
ANSUL MICRO-K MODEL 11K-E CONDENSED AEROSOL FIRE EXTINGUISHING GENERATORS
It has recently been brought to our attention that a pilot vessel, operating under the Code of Practice for the Safety of Small Workboats and Pilot Boats, suffered a small fire in the machinery space, protected by a fixed aerosol fire suppression system which failed to operate correctly.
Click here to download a printable version of this safety alert (PFD 79Kb)
The fire suppression system consisted of three Ansul Micro-K Model 11K-E Condensed Aerosol generators and one Stat-X Model G500 Condensed Aerosol generator connected in a series circuit, with a diode across each generator to allow for continuity should one generator become open circuit.
Investigation showed that the three Micro-K units had failed to operate, but the Stat-X unit operated correctly to extinguish the fire.
Close inspection of the Micro-K units showed deficiencies in the firing electrical wiring and connections, and displacement of the plastic cover on one unit, which may allow moisture to contaminate the aerosol compound which is hygroscopic (moisture absorbent).
As a result of this investigation, we strongly recommend that all Micro-K Model 11K-E Condensed Aerosol generator systems are inspected at the earliest opportunity, and at regular intervals thereafter, for the following:-
Plastic cover and tamper seal tape

ANSUL MICRO-K STANDARD AEROSOL GENERATOR
For further information please contact:-
Marine Technology Unit,
Maritime & Coastguard Agency
Tel: +44 (0)23 8032 9100
For further information please contact Shipping Safety Branch, Maritime & Coastguard Agency
Tel: +44 (023) 8032 9100
Issued: December 2008