Regulation 9. Containment of fire

7    Ventilation systems

7.1    Duct and dampers

7.1.1    Ventilation ducts shall be of non combustible material. However, short ducts, not generally exceeding 2 m in length and with a free cross sectional area*

* not exceeding 0.02 m², need not be non combustible subject to the following conditions:

7.1.1.1    the ducts are made of a material which has low flame spread characteristics;

7.1.1.2    the ducts are only used at the end of the ventilation device; and

7.1.1.3    the ducts are not situated less than 600 mm, measured along the duct, from an opening in an "A" or "B" class division, including continuous "B" class ceiling.

7.1.2    The following arrangements shall be tested in accordance with the Fire Test Procedures Code:

7.1.2.1    fire dampers, including their relevant means of operation; and

7.1.2.2    duct penetrations through "A" class divisions. However, the test is not required where steel sleeves are directly joined to ventilation ducts by means of riveted or screwed flanges or by welding.

7.2    Arrangement of ducts

7.2.1    The ventilation systems for machinery spaces of category A, vehicle spaces, ro-ro spaces, galleys, special category spaces and cargo spaces shall, in general, be separated from each other and from the ventilation systems serving other spaces, except that the galley ventilation systems on cargo ships of less than 4,000 gross tonnage and in passenger ships carrying not more than 36 passengers need not be completely separated, but may be served by separate ducts from a ventilation unit serving other spaces. In any case, an automatic fire damper shall be fitted in the galley ventilation duct near the ventilation unit. Ducts provided for the ventilation of machinery spaces of category A, galleys, vehicle spaces, ro-ro spaces or special category spaces shall not pass through accommodation spaces, service spaces or control stations unless they comply with the conditions specified in paragraphs 7.2.1.1.1 to 7.2.1.1.4 or 7.2.1.2.1 and 7.2.1.2.2 below:

7.2.1.1.1    the ducts are constructed of steel having a thickness of at least 3 mm and 5 mm for ducts the widths or diameters of which are up to and including 300 mm and 760 mm and over respectively and, in the case of such ducts, the widths or diameters of which are between 300 mm and 760 mm having a thickness obtained by interpolation;

7.2.1.1.2    the ducts are suitably supported and stiffened;

7.2.1.1.3    the ducts are fitted with automatic fire dampers close to the boundaries penetrated; and

7.2.1.1.4    the ducts are insulated to "A-60" class standard from the machinery spaces, galleys, vehicle spaces, ro-ro spaces or special category spaces to a point at least 5 m beyond each fire damper;

or

7.2.1.2.1    the ducts are constructed of steel in accordance with paragraphs 7.2.1.1.1 and 7.2.1.1.2; and

7.2.1.2.2    the ducts are insulated to "A-60" class standard throughout the accommodation spaces, service spaces or control stations;

except that penetrations of main zone divisions shall also comply with the requirements of paragraph 4.1.1.8.

7.2.2    Ducts provided for ventilation to accommodation spaces, service spaces or control stations shall not pass through machinery spaces of category A, galleys, vehicle spaces, ro-ro spaces or special category spaces unless they comply with the conditions specified in paragraphs 7.2.2.1.1 to 7.2.2.1.3 or 7.2.2.2.1 and 7.2.2.2.2 below:

7.2.1.1.1    the ducts where they pass through a machinery space of category A, galley, vehicle space, ro ro space or special category space are constructed of steel in accordance with paragraphs 7.2.1.1.1 and 7.2.1.1.2;

7.2.1.1.2    automatic fire dampers are fitted close to the boundaries penetrated; and

7.2.1.1.3    the integrity of the machinery space, galley, vehicle space, ro-ro space or special category space boundaries is maintained at the penetrations;
or

7.2.1.2.1    the ducts, where they pass through a machinery space of category A, galley, vehicle space, ro-ro space or special category space, are constructed of steel in accordance with paragraphs 7.2.1.1.1 and 7.2.1.1.2; and

7.2.1.2.2    the ducts are insulated to "A-60" standard within the machinery space, galley, vehicle space, ro ro space or special category space;

except that penetrations of main zone divisions shall also comply with the requirements of paragraph 4.1.1.8.

7.3    Details of duct penetrations

7.3.1    Where a thin plated duct with a free cross-sectional area equal to, or less than, 0.02 m² passes through "A" class bulkheads or decks, the opening shall be lined with a steel sheet sleeve having a thickness of at least 3 mm and a length of at least 200 mm, divided preferably into 100 mm on each side of the bulkhead or, in the case of the deck, wholly laid on the lower side of the decks pierced. Where ventilation ducts with a free cross-sectional area exceeding 0.02 m² pass through "A" class bulkheads or decks, the opening shall be lined with a steel sheet sleeve. However, where such ducts are of steel construction and pass through a deck or bulkhead, the ducts and sleeves shall comply with the following:

7.3.1.1    The sleeves shall have a thickness of at least 3 mm and a length of at least 900 mm. When passing through bulkheads, this length shall be divided preferably into 450 mm on each side of the bulkhead. These ducts, or sleeves lining such ducts, shall be provided with fire insulation. The insulation shall have at least the same fire integrity as the bulkhead or deck through which the duct passes; and

7.3.1.2    Ducts with a free cross sectional area exceeding 0.075 m² shall be fitted with fire dampers in addition to the requirements of paragraph 7.3.1.1. The fire damper shall operate automatically, but shall also be capable of being closed manually from both sides of the bulkhead or deck. The damper shall be provided with an indicator which shows whether the damper is open or closed. Fire dampers are not required, however, where ducts pass through spaces surrounded by "A" class divisions, without serving those spaces, provided those ducts have the same fire integrity as the divisions which they pierce. Fire dampers shall be easily accessible. Where they are placed behind ceilings or linings, these ceilings or linings shall be provided with an inspection door on which a plate reporting the identification number of the fire damper is provided. The fire damper identification number shall also be placed on any remote controls required.

7.3.2    Ventilation ducts with a free cross-sectional area exceeding 0.02m² passing through "B" class bulkheads shall be lined with steel sheet sleeves of 900 mm in length, divided preferably into 450 mm on each side of the bulkheads unless the duct is of steel for this length.

7.4    Ventilation systems for passenger ships carrying more than 36 passengers

7.4.1    The ventilation system of a passenger ship carrying more than 36 passengers shall be in compliance with the following additional requirements.

7.4.2    In general, the ventilation fans shall be so disposed that the ducts reaching the various spaces remain within the main vertical zone.

7.4.3    Where ventilation systems penetrate decks, precautions shall be taken, in addition to those relating to the fire integrity of the deck required by paragraphs 3.1 and 4.1.1.5, to reduce the likelihood of smoke and hot gases passing from one 'tween deck space to another through the system. In addition to insulation requirements contained in paragraph 7.4, vertical ducts shall, if necessary, be insulated as required by the appropriate tables 9.1 and 9.2.

7.4.4    Except in cargo spaces, ventilation ducts shall be constructed of the following materials:

7.4.4.1    ducts not less than 0.075 m² in free cross-sectional area and all vertical ducts serving more than a single 'tween-deck space shall be constructed of steel or other equivalent material;

7.4.4.2    ducts less than 0.075 m² in free cross-sectional area other than the vertical ducts referred to in paragraph 7.4.4.1, shall be constructed of non combustible materials. Where such ducts penetrate "A" or "B" class divisions, due regard shall be given to ensuring the fire integrity of the division; and

7.4.4.3    short lengths of duct, not in general exceeding 0.02m² in free cross-sectional area nor 2 m in length, need not be non combustible provided that all of the following conditions are met:

7.4.4.3.1    the duct is constructed of a material which has low flame spread characteristics;

7.4.4.3.2    the duct is used only at the terminal end of the ventilation system; and

7.4.4.3.3    the duct is not located closer than 600mm measured along its length to a penetration of an "A" or "B" class division, including continuous "B" class ceilings.

7.4.5    Stairway enclosures shall be ventilated and served by an independent fan and duct system which shall not serve any other spaces in the ventilation systems.

7.4.6    Exhaust ducts shall be provided with hatches for inspection and cleaning. The hatches shall be located near the fire dampers.

7.5    Exhaust ducts from galley ranges

7.5.1    Requirements for passenger ships carrying more than 36 passengers

Exhaust ducts from galley ranges shall meet the requirements of paragraphs 7.2.1.2.1 and 7.2.1.2.2 and shall be fitted with:

7.5.1.1    a grease trap readily removable for cleaning unless an alternative approved grease removal system is fitted;

7.5.1.2    a fire damper located in the lower end of the duct which is automatically and remotely operated, and, in addition, a remotely operated fire damper located in the upper end of the duct;

7.5.1.3    a fixed means for extinguishing a fire within the duct;

7.5.1.4    remote-control arrangements for shutting off the exhaust fans and supply fans, for operating the fire dampers mentioned in paragraph 7.5.1.2 and for operating the fire-extinguishing system, which shall be placed in a position close to the entrance to the galley. Where a multi-branch system is installed, a remote means located with the above controls shall be provided to close all branches exhausting through the same main duct before an extinguishing medium is released into the system; and

7.5.1.5    suitably located hatches for inspection and cleaning.

7.5.2    Requirements for cargo ships and passenger ships carrying not more than 36 passenger

7.5.2.1    Where they pass through accommodation spaces or spaces containing combustible materials, the exhaust ducts from galley ranges shall be constructed of "A" class divisions. Each exhaust duct shall be fitted with:

7.5.2.1.1    a grease trap readily removable for cleaning;

7.5.2.1.2    a fire damper located in the lower end of the duct;

7.5.2.1.3    arrangements, operable from within the galley, for shutting off the exhaust fans; and

7.5.2.1.4    fixed means for extinguishing a fire within the duct.

Guidance 9

G58    Fire dampers

G58.1    Manual control of dampers

G58.1.1    Manual control of a fire damper is to be independent of and capable of overriding any automatic means of control.

G58.1.2    Manual closing is normally by means of a handle linked directly to the damper blade spindle, but may be achieved by local operation of the fire damper by means of a fail-safe electrical switch or pneumatic release (spring loaded, etc.), on both sides of the division, with indication of fire damper status.

G58.2    Automatic closure of dampers

G58.2.1    When a fire damper is required to be closed automatically, the means of operation shall be situated inside the coaming or spigot such that it can be activated by hot gases passing through the ventilation ducting. The MCA is prepared to accept any additional means of operating the damper automatically, subject to compliance with preceding paragraphs.

G58.2.2    The means of operation shall be activated at temperatures within the range of 68°C to 79°C inclusive, except that in exhaust ducts serving spaces with high ambient temperatures such as galleys and drying rooms, the temperature at which the means of operation is activated may be increased to not more than 30°C above the maximum deckhead temperature.

G58.2.3    When the means of operating a fire damper automatically is a spring and fusible link, the link is required to be capable of being released manually from outside the duct by withdrawing the pin over which the link is hooked except that any other effective means of release would be considered.

G58.2.4    A pneumatic or electrical system must be such that the fire damper closes on release of the air or failure of any one of the components or power supply.

G58.3    Manual operation of dampers from both sides of a division

G58.3.1    In order to satisfy the requirements to operate a fire damper from both sides of a bulkhead or deck as indicated in the Regulations, a damper may be fitted on each side of the division within the coaming or spigot, the dampers being operated independently of each other. Only one of the two dampers need be capable of being closed automatically when automatic operation is required by the Regulations.

G58.3.2    Alternatively a single manual or automatic damper as appropriate may be fitted on one side of the bulkhead or deck, arranged for local manual operation, and in addition for manual operation from the blind side of such a division using a suitable linkage. The instructions of this section should be complied with at both operating positions.

G58.4    Open/closed indicator (on damper)

G58.4.1    Each damper is required by the Regulations to be fitted with a visible indicator to show whether the damper is in the open or closed position. The method of indication should be visible from the operating position.

G59    Components clear of coaming

G59.1 The manual and automatic controls, indicator, access panels and any other component should be sufficiently clear of the coaming to enable the coaming to be properly insulated.

G60    Damper controls clear of obstructions

G60.1    Manual and automatic controls of a damper are to be clear of the division, the insulation on the division or any other obstruction when the damper is in the open and closed positions.

G61    Ducts passing through 'A' Class divisions

G61.1    Attention is also drawn to the guidance dealing with Regulations referring specifically to the fitting of fire dampers in ventilation ducts passing through 'A' Class divisions and ventilation systems in general.

G61.2    The other spaces referred to in paragraph 7.2.1 are accommodation spaces, service spaces and control stations.

G61.3    Where the ventilation ducting serving a space or group of spaces fitted with a fixed gas fire-extinguishing system passes through any space not served by the system, the ducting should be of steel and of gas tight construction.

G61.4    The ventilation system serving a space in which gas cylinders are stored should not serve any other space and should be capable of freeing the space of any gas which may leak from the cylinders. Any ducting of such a system which passes through any other space should be of steel and of gas tight construction.

G62    Systems within main zones

G62.1    Wherever practicable the ventilation system leading from each ventilation fan shall be within one main vertical or horizontal zone. The fan room should also be within the same main zone otherwise an excessive number of fail-safe automatic closing fire dampers may be required where ducts penetrate the main zone division.

G63    Smoke control

G63.1    Where the arrangement of ducts and fire dampers in a ventilation system is such that smoke and hot gases may pass from one 'tween-deck to another through the system, a damper should be fitted in the duct on the upper side of the deck separating the 'tween-decks. The dampers may be simple manually controlled steel dampers fitted in a readily accessible position, and need not be of a fire tested type. Alternatively when the ducts are of steel their closure may be achieved by the shutting of punkah louvres or grilles fitted to the openings in the branch trunking within a 'tween-deck.

G63.2    Where individual ducts serve a single 'tween-deck the smoke damper may be at the fan unit or other location providing suitable isolation.

G64    Vertical ducts

G64.1    Paragraph 7.4.3 requires vertical ducts to be insulated as required by the tables in paragraph 2.2.3. Compliance with this Regulation may be achieved in the case of vertical ducts which are fitted with fire dampers, by insulating each damper coaming to the 'A' Class standard of the deck through which the duct passes.

G64.2    Vertical ducts having a cross sectional area not exceeding 0.075m² which pass through 'A' Class decks other than those which are main zone divisions, are not required to be fitted with fire dampers. Such vertical ducts should be insulated to the same 'A' Class standard as the decks through which they pass by continuing the insulation fitted to the deck plating along the ducts for a distance of not less than 450mm from the deck plating.

G64.3    Openings for recirculation of air or balancing a ventilation system may be provided between corridors in separate tween decks provided that they are trunked into the corridors with no openings into the ceiling or lining voids. In addition they should comply with the constructional requirements and the requirements for the provision of fire and smoke dampers of paragraph 7. They should normally be fitted with sliding or hinged steel shutters at their ends.

G64.4    The recommended thickness of the steel coamings incorporating fire dampers for closing openings in ventilation ducts is indicated in the following table:


Table 9.1

G64.5    When any duct not exceeding 0.075m² in cross sectional area, passes through an insulated 'A' Class division the duct or steel sleeve should be insulated for a distance of not less than 380mm from the division with 'A' Class mineral wool insulation having a thickness equivalent to that fitted over the plating of the division.

G64.6    When any duct exceeding 0.075m² in cross sectional area, passes through an insulated 'A' Class division the steel coaming incorporating the fire dampers should be insulated with an 'A' Class mineral wool insulation having a thickness equivalent to that fitted over the plating of the division as indicated in figures 9.21 and 9.22. The insulation is to be attached by means of welded steel pins, wire netting and spring steel washers.

Note: Illustrations of insulation fitted to coamings are on following pages.

G65    Ducts in service trunks

G65.1    Where ventilation ducts are grouped in a service trunk only the service trunk need be insulated at the deck penetration; provided the trunk is closed and has A Class integrity at all points.


G66    Fire resisting ducts

G66.1    Fire dampers are not required to be fitted in a duct which passes through a space surrounded by 'A' Class divisions and has no openings into the space, subject to following main paragraph and provided that the duct:

G66.1.1    has the same thickness as a duct as indicated in paragraph 7.2.1.1.1;

G66.1.2    is adequately supported and stiffened; and

G66.1.3    is insulated to the same 'A' Class standard as the divisions through which it passes or to the higher standard when the divisions have differing 'A' Class standards. This is illustrated by figure 9.23 below.

G66.2    The dispensing of fire dampers in this manner shall not apply when a duct passes through a main zone division, because paragraph 4.1.1.8 still applies.

G66.3    Notwithstanding the preceding main paragraph when a duct serves spaces bounded by 'A' Class divisions and which are situated on each side of another space into which the duct has no openings, fire dampers are still required to be fitted at each end of the 'A' Class ducting in order to maintain the integrity of the two outer spaces from each other. This is illustrated by figure 9.24.

G67    Ducts passing through 'B' Class divisions (paragraph 7.3.2)

G67.1    Ventilation ducts passing through 'B' Class bulkheads, ceilings or linings should be treated as indicated in the following table;

Table 9.2

Cross sectional Area of ductType of ductTreatment
Not exceeding 0.02m²Steel ducts other than single skinned spiroducts.To be collared to the division. The collars may be of steel or of the same material and thickness as the division.
 Single skinned spiroducts. Aluminium alloy ducts.To be passed through a steel sleeve having a length and thickness of not less than 600mm and 1.0mm respectively collared to the division. The collars may be of steel or of the same material and thickness as the division. The gap between the sleeve and the duct should be effectively packed with a non-combustible material and the ends sealed with a suitable flexible sealant.
Exceeding 0.02m² but not exceeding 0.075m²Steel ducts other than single skinned spiroducts.To be collared to the division with steel collars.
 Single skinned spiroducts. Aluminium alloy ducts.To be passed through a steel sleeve having a length and thickness of not less than 900mm and 1.0mm respectively collared to the division. The collars are to be of steel. The gap between the sleeve and the duct should be effectively packed with a non-combustible material and the ends sealed with a suitable flexible sealant.
Exceeding 0.075m²Steel ducts other than spiroducts.To be collared to the division with steel collars.
 Double and single skinned spiroducts. Aluminium alloy ducts.To be passed through a sleeve having a length and thickness of 900mm and 1.5mm respectively collared to the division. The collars are to be of steel. The gap between the sleeve and the duct should be effectively packed with a non-combustible material and the ends sealed with a suitable flexible sealant.

G68    Ducts from machinery of Category A, galleys etc. (Paragraph 7.2.1)

G68.1    It should be noted that double and single skinned spiroducts are precluded from use in the situations referred to because they are not constructed of steel of the required thickness.

G68.2    The automatic closing fire damper required by paragraph 7.2.1.1.3 should be fitted on the opposite side of the boundary penetrated to that of the spaces which it serves. The manual controls of the dampers should be readily accessible and the operating position clearly marked.

G68.3    Care should be taken to ensure that the A-60 standard of the portion of ducting which is required by paragraph 7.2.1.1.4 to be insulated, is not impaired where the ducting passes through a deck or adjoins another structure. It should be borne in mind that the intention of the requirement is to protect the accommodation spaces etc. from a fire in the machinery space of Category A, galley etc.

G68.4    When the measures specified in paragraph 7.2.1.2.2 or 7.2.2.2.2 are adopted and the boundary of the machinery space of Category A, galley, Ro-Ro space or special category space which is being penetrated by the duct is a main zone division, in addition to the duct being insulated for its full length to A-60 standard, paragraph 4.1.1.8 must also be complied with.

G68.5    Similar care with insulation should be taken when the alternative method of protecting accommodation spaces etc. indicated in paragraph 7.2.1.2.1 and 7.2.1.2.2, is adopted.

G69    Ducts from accommodation spaces etc. (Paragraph 7.2.2)

G69.1    See guidance G9.68, which applies in a similar manner.

G70    Galley ventilation

G70.1    The automatic closing fire damper referred to in paragraph 7.5.2.1.2 should be positioned immediately above the grease trap and the fixed means of extinguishing a fire referred to in paragraph 7.5.2.1.4 should be capable of extinguishing a fire situated anywhere above it from the exhaust duct. The fire damper should be provided with manual control operable from an accessible position clear of the equipment which the exhaust duct serves.

G70.2    In all cases when an exhaust duct is fitted with branches serving different items of galley equipment, the requirements of paragraph 7.5.2.1.4 should apply to each branch. In such cases remote control of the fire dampers in the exhaust trunk branches may be necessary; even in those ships which are not required to comply with paragraph 7.5.2.1.2. Where compliance with these standards is not necessary because a galley exhaust duct does not pass through accommodation spaces or spaces containing combustibles e.g. when the duct goes directly to the open air from the galley, then regulations 5.2.1.1 and 5.2.1.2 should be complied with in respect of stopping the fan and providing a means of closure at the duct outlet. It would be sensible in such a case to fit a grease trap in the duct.

G71    Ducts passing through 'A' Class divisions (on cargo ships and tankers)

G71.1    See guidance G9.61 which also applies in a similar manner to cargo ships and tankers.

G72    Fire resisting ducts (on cargo ships and tankers)

G72.1    See guidance G9.66 which also applies in a similar manner to cargo ships and tankers except that paragraph 66.3 does not apply.

G73    Openings for recirculating or exhausting air or balancing systems

G73.1    Paragraph 4.2.3, for cargo ships, paragraph 4.1.2.1, for passenger ships, permits openings in the lower part of 'B' Class doors through which air from cabins or similar spaces and from cabins and public spaces respectively may be taken via the corridors and ducting to the air conditioning machinery room for recirculation or to the atmosphere. 'B' Class bulkheads should not be penetrated by openings other than those in the lower part of the doors or within ducting irrespective of the openings being fitted with shutters or dampers. Open-ended steel coamings should not be regarded as ducting.

G73.2    Air from spaces surrounded by 'A' Class divisions should not be exhausted directly into corridors for recirculating or for return to the atmosphere through openings or open-ended coamings irrespective of the openings or coamings being fitted with shutters or dampers. Such spaces should be fitted with exhaust ducting to the fan room or to the atmosphere. Similarly high risk spaces such as galleys should not be provided with recirculating, balancing or exhaust openings or open-ended coamings into adjacent accommodation spaces.

G73.3    Openings for recirculation of air or balancing a ventilation system may be provided between corridors in separate 'tween decks provided that they are trunked into the corridors with no openings into the ceiling or lining voids. Also, they should comply with constructional requirements (including the provision of fire and smoke dampers) of paragraph 7. They should normally be fitted with sliding or hinged steel shutters at their ends.